00135974_0
Expansion module BACnet MS/TP, Modbus RTU


00133235_0
BACnet-MS/TP-Schnittstelle


00134484_0
Modbus-Schnittstelle


00135974_0
00133235_0
00134484_0

EM-BAC-MOD

BACNET AND MODBUS INTERFACE FOR UNIVERSAL CONTROLLERS AND ADAPTER MODULES

Expansion module for UNIVERSAL fume cupboard controllers, room controllers, extract air controllers, supply air controllers, and adapter modules, for the integration of rooms or individual volume flow controllers with the central BMS

  • Switching between BACnet MS/TP and Modbus RTU
  • BACnet Standardised Device Profile (Annex L)
  • Modbus interface with individual data registers
  • Native BACnet interface by integrating the expansion module with EASYLAB components
  • Easy retrofitting
  • Double-stack terminal blocks for the EIA-485 bus
  • Equipment address and data transfer parameters can be defined


Interface to central BMS

  • When used on a controller with active room management function (RMF) the module provides also data points for the entire room, e.g. for total volume flows or consolidated alarms
  • When used on a single controller: data points for volume flow rate, alarm, damper blade position, or others
  • Centralised operating mode default setting, e.g. night-time operation

Application

Application

  • Expansion module Type EM-BAC-MOD for the EASYLAB system
  • BACnet-MS/TP or Modbus RTU interface to the central BMS
  • Data points for individual controllers or for the room
  • Room interface: Default setting of room operating modes within the EASYLAB system, increase or reduction of the air change rate, readout of the actual room operating values or evaluated damper blade positions, consolidated alarms
  • Controller interface: Operating mode default setting for a single fume cupboard controller, readout of individual operating values such as volume flow rates for single controllers, or individual alarms
  • Can be used with fume cupboard, supply air, extract air or differential pressure controller EASYLAB TCU3 and with adapter module TAM
  • For use in laboratories, clean rooms in the pharmaceutical and semiconductor industries, operating theatres, intensive care units, and offices with very demanding control requirements
  • Factory mounted or for retrofitting into the EASYLAB base component casing

Special characteristics

  • Ready for installation, can be easily connected to the main PCB
  • Interface for EIA-485 networks BACnet MS/TP and Modbus RTU
  • BACnet Protocol Revision 12.0
  • Only standard BACnet objects or Modbus registers are used for communication
  • Data interface for an EASYLAB controller or for an EASYLAB room with different functional profiles
  • Hardware switch to enter network addresses and communication parameters (no communication software required)

Description

Parts and characteristics

  • Microprocessor with setup programme stored in nonvolatile memory
  • EIA-485 communication interface
  • Slide switch to switch between BACnet and Modbus communication protocols
  • Two address switches, X and Y, to set equipment addresses 1-99
  • 8-way DIP switches to adjust the communication parameter
  • Double-stack terminal blocks for the EIA-485 network (simple wiring)
  • Two indicator lights indicate communication and errors, respectively
  • Connection to update the firmware
  • EIA-485 terminal resistor that can be activated

Construction features

  • PCB dimensions and fixing points correspond to the EASYLAB main PCB and the casing
  • Fixing with screws
  • Pin header to connect the module to the main PCB of the TCU3 or TAM

Information technique

Function, Technical data, Specification text, Order code, Related products

  • Function
  • Technical data
  • Specification text
  • Order code
EM-BAC-MOD 00133131_0
① Switch to select BACNet MS/TP or Modbus RTU protocol
② Plug base for connection with the EASYLAB main PCB
③ Switches to set the network addresses, 01-99
④ DIP switch to set communications parameters
⑤ Network connection (EIA-485)
⑥ Connection to update the firmware
⑦ Indicator lights


Functional description

The expansion module EM-BAC-MOD is used to integrate EASYLAB controllers Type TCU3 or EASYLAB adapter modules Type TAM into a BACnet (MS/TP) network and in this way connect them to the central BMS.

The BACnet or Modbus interface supports the EASYLAB room operating mode concept. It is possible to set operating mode defaults in order to control different volume flow rates for daytime and night-time operation; it is also possible to increase or reduce the air change rate (volume flow rate setpoint change), e.g. to influence the room temperature.

Using the BACnet or Modbus interface, an individual alarm management system can be set up by consolidating configurable EASYLAB alarms. The interface also enables the transfer of actual operating values such as volume flow rates and damper blade position for a controller or for all controllers in a room.

Supply voltage

5 V DC from controller or adapter module

Communication interface

EIA-485 standard

Protocol

BACnet MS/TP standard rev. 12 or Modbus RTU

Data transmission speeds

BACnet: 9600, 19200, 38400, 76800 Bd, Modbus: 9600, 19200, 38400, 57600 Bd

Parity checks for data transmission security

None, odd, even

Configurable network addresses

01 … 99

Operating temperature

0 – 50 °C

IEC protection class

III (protective extra-low voltage)

Protection level

IP 20

EC conformity

EMC according to 2004/108/EC

Dimensions (B × H × T)

78 × 65 ×100 mm


Expansion module to supplement an EASYLAB base component (controller TCU3 or adapter module TAM) with a BACnet or Modbus interface to link rooms or individual volume flow controllers to the central BMS.

The expansion module includes an interface for EIA-485 networks that can be used for BACnet MS/TP or Modbus RTU (switching), a switch to enter communication parameters, a connection to update the firmware, and indicator lights.

Special characteristics

  • Ready for installation, can be easily connected to the main PCB
  • Interface for EIA-485 networks BACnet MS/TP and Modbus RTU
  • BACnet Protocol Revision 12.0
  • Only standard BACnet objects or Modbus registers are used for communication
  • Data interface for an EASYLAB controller or for an EASYLAB room with different functional profiles
  • Hardware switch to enter network addresses and communication parameters (no communication software required)

Technical data

  • Communication interface: EIA-485 standard
  • Protokoll: BACnet MS/TP standard rev. 12 or Modbus RTU
  • Data transmission speeds: BACnet: 9600, 19200, 38400, 76800 baud, Modbus: 9600, 19200, 38400, 57600 baud
  • Parity checks for data security: none, odd, even
  • Configurable network addresses: 01 … 99
  • Operating temperature: 0 to 50 °C
  • IEC protection class: III (protective extra-low voltage)
  • Protection level: IP 20
  • EC conformity: EMC to 2004/108/EC

Data points for a single controller

  • Volume flow rate actual and setpoint values
  • Damper blade position
  • Operating mode
  • Alarm/status messages
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Number of controllers
  • Integration of volume flows


Additional data points for a fume cupboard controller

  • Operating mode default setting for the fume cupboard controller equipped with the expansion module
  • Selection of priority for operating mode default setting
  • Face velocity actual value and setpoint value (only for fume cupboard controllers with face velocity transducer, equipment function FH-VS)

Data points for an EASYLAB room

  • Operating mode default setting for the room: Just one data point is required to set the default operating mode for all controllers in a room
  • Selection of priority for operating mode default setting (central BMS or room)
  • Room operating mode
  • Volume flow rate setpoint change (by the central BMS, for example) for an external temperature or differential pressure control
  • Setpoint value switching for differential pressure control: Switching between two differential pressure setpoint values
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Room differential pressure actual and setpoint values
  • Room pressure alarm
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs
  • Configurable consolidated alarm (operating statuses, hardware faults)

  • Any attachments are to be defined with the order code of the VAV terminal unit.
  • Retrofit possible

 

Single controller, EASYLAB room, BACnet interface, Modbus interface, Product details

  • Single controller
  • EASYLAB room
  • BACnet interface
  • Modbus interface
  • Product details
LonWorks, BACnet or Modbus interface on a single controller, e.g. fume cupboad controller 00183220_0
BMS central building management system
RMF Controller with active room management function
ROM Room operating mode, from the room control panel
IOM Individual operating mode, transmitted via BACnet or Modbus interface


Single controller

Interface for one EASYLAB controller

  • Local data interface for a fume cupboard controller, supply air controller, extract air controller, or adapter module TAM


Data points for a single controller

  • Volume flow rate actual and setpoint values
  • Damper blade position
  • Operating mode
  • Alarm/status messages
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs


Additional data points for a fume cupboard controller

  • Operating mode default setting for the fume cupboard controller equipped with the expansion module
  • Selection of priority for operating mode default setting
  • Face velocity actual value and setpoint value (only for fume cupboard controllers with face velocity transducer, equipment function FH-VS)

LonWorks, BACnet or Modbus interface for an EASYLAB room, e.g. on a room controller with active room management function 00183226_0
BMS central building management system
RMF Controller with active room management function
ROM Room operating mode, from the controller with room management function


EASYLAB room

Interface for one EASYLAB room

  • Local data interface for a TCU3 room controller (supply air or extract air) or TAM adapter module with active room management function
  • Room management function reduces the required number of network data points and hence the commissioning costs
  • Transmission of local data for the single controller and for the room


Data points for an EASYLAB room controller

  • Operating mode default setting for the room: Just one data point is required to set the default operating mode for all controllers in a room
  • Selection of priority for operating mode default setting (central BMS or room)
  • Room operating mode
  • Volume flow rate setpoint change (by the central BMS, for example) for an external temperature or differential pressure control
  • Setpoint value switching for differential pressure control: Switching between two differential pressure setpoint values
  • Total supply air and total extract air actual values (room)
  • Evaluated damper blade positions for all controllers in a room
  • Room differential pressure actual and setpoint values
  • Room pressure alarm
  • Number of controllers within the EASYLAB system
  • Integration of volume flows
  • Status of the digital inputs and outputs
  • Configurable consolidated alarm (operating statuses, hardware faults)
  • Control input signal for sun protection/blinds (to be provided by others)

BACnet interface

Application

The expansion module EM-BAC-MOD supports the following interface functions on an EASYLAB controller TCU3 or an adapter module TAM if the BACnet protocol has been selected:

  • Native BACnet, i.e. the BACnet interface is implemented on the field module (EASYLAB volume flow controller)
  • External hardware components such as physical gateways are not required
  • BACnet interface documentation includes the following documents: Protocol Implementation Conformance Statement (PICS), BACnet Interoperability Building Blocks Supported (BIBBS), as well as a description of the device object and the supported objects
  • For more information on each data point see the Details section

BACnet PICS (Protocol Implementation Conformance Statement) – Overview

Principal categories Values

Date

2014-01-21

Vendor name

TROX GmbH

Vendor identifier

329

Product name

EM-BAC-MOD

Model no.

M536HD7

Application

4.0

Firmware Revison

4.0

BACnet Protocol Revision

12

Standarised Device Profile

BACnet Application Specific Controller (B-ASC)

Segmentation Capability

No

Data Link Layer Options

MS/TP master (Clause 9), Baudrates 9600, 19200, 38400, 76800

Device Address Binding

No

Network Security Options

Non-secure Device - is capable of operating without BACnet Network Security

Character Sets Supported

ISO 10646 (UTF-8)


Configuration switches

Hexadecimal Switches X, Y Network address





DIP Switch 1

OFF

ON



Controller

EASYLAB TCU3

Other








DIP Switch 2

OFF

ON

OFF

ON

DIP Switch 3

OFF

OFF

ON

ON

Baud rate

9600

19200

38400

76800


BIBBS - BACnet Interoperability Building Blocks Supported

Data Sharing-ReadProperty-B

DS-RP-B

Data Sharing-WriteProperty-B

DS-WP-B

Data Sharing-COV-Unsolicited-B

DS-COVU-B

Device Management-Dynamic Device Binding-B

DM-DDB-B

Device Management-Dynamic Object Binding-B

DM-DOB-B

Device Management-Device Communication Control-B

DM-DCC-B

Device Management-ReinitialiseDevice-B

DM-RD-B


DeviceObject

Property Value Access

Object identifier

Device instance; default instance = 32900 + set network address

WR, RD; E

Object name

Default="EM-BACnet"; project-specific description can be entered, 62 characters max.

WR, RD; E

Object type

Device (8)

RD

System_Status

OPERATIONAL (0)

RD

Vendor_Name

"TROX GmbH"

RD

Vendor_Identifier

329

RD

Model_Name

"EM-BAC-MOD"

RD

Description

Default = “EASYLAB”; description can be entered, 126 characters max.

WR, RD; E

Location

Default = ""; description can be entered, 62 characters max.

WR, RD; E

Firmware_Revision

“4.0” (EASYLAB)

RD

Application_Software_Version

“4.0” (EASYLAB)

RD

Protocol_Version

1

RD

Protocol_Revision

12

RD

Protocol Services Supported

Who-is, Who-has, Read-Property, Write-Property, Device-communication-control, Reinitialize-device

RD

Protocol_Object_Types_Supported

DEVICE, ANALOG_VALUE, BINARY_VALUE, MULTISTATE_VALUE

RD

Object_List

EASYLAB: device, analog-value 1…36, binary-value 1…30, multistate-value 1…8

RD

Max_ADPU_Length_Accepted

480

RD

Segmentation_Supported

NO_SEGMENTATION (3)

RD

APDU_Timeout

10000

RD

Number_Of_APDU_Retries

3

RD

Device_Address_Binding

RD

Database_Revision

0

RD

Description

Controller Type “EASYLAB”

RD

Max_Master

Default 127

WR, RD; E

Max_Info_Frames

Default 1

WR, RD; E


Multistate Value Objects

Instance Designation Unit Access
Instance Designation TCU3 TAM Access
Instance Designation Available with equipment function Access
Instance Designation FH RR RR RMF EC, SC TAM TAM RMF Access

1

COVU mode

x

x

x

x

x

x

WR, RD

2

Mode

x1


x



x

WR, RD

3

ModeAct

x

x

x

x



RD

4

RoomModeAct



x



x

RD

5

SwitchPos

x






RD

6

Sunblind



x



x

WR, RD

7

SC_SetLockHighPrio







WR, RD

8

SC_GetLockHighPrio







RD

1 only for individually selected operating mode (stand-alone operation)

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Analogue Value Objects

Instance Designation Unit Access
Instance Designation Unit TCU3 TAM Access
Instance Designation Unit Available with equipment function Access
Instance Designation Unit FH RR RR RMF EC, SC TAM TAM RMF Access

1

VolflowSet

l/s (87)

x

x

x

x


x

RD

2

VolflowAct

l/s (87)

x

x

x

x


x

RD

3

VolTotalExh

l/s (87)

x

x

x

x

x

x

RD

4

VolTotalSup

l/s (87)

x

x

x

x

x

x

RD

5

PressSet

Pa (53)



x



x

RD

6

PressAct

Pa (53)



x



x

RD

7

VelocitySet

m/s (74)

x






RD

8

VelocityAct

m/s (74)

x






RD

9

WireSensorPos

percent (98)

x






RD

10

DampPos

percent (98)

x

x

x

x



RD

11

DampPosMax_FH

percent (98)

x

x

x

x

x

x

RD

12

DampPosMin_FH

percent (98)

x

x

x

x

x

x

RD

13

DampPosMax_RE

percent (98)

x

x

x

x

x

x

RD

14

DampPosMin_RE

percent (98)

x

x

x

x

x

x

RD

15

DampPosMax_TE

percent (98)

x

x

x

x

x

x

RD

16

DampPosMin_TE

percent (98)

x

x

x

x

x

x

RD

17

DampPosMax_RS

percent (98)

x

x

x

x

x

x

RD

18

DampPosMin_RS

percent (98)

x

x

x

x

x

x

RD

19

VolOffset_T

percent (98)



x



x

WR, RD

20

VolOffset_P

percent (98)



x



x

WR, RD

21

SystemDevices

no units (95)

x

x

x

x

x

x

RD

22

VolflowExh

l/s (87)

x

x

x


x

x

WR, RD

23

VolflowSup

l/s (87)

x

x

x


x

x

WR, RD

24

SC_SetPos

percent (98)







WR, RD

25

SC_GetPos

percent (98)







RD

26

DampPosMax_EC

percent (98)

x

x

x

x

x

x

RD

27

DampPosMin_EC

percent (98)

x

x

x

x

x

x

RD

28

DampPosMax_SC

percent (98)

x

x

x

x

x

x

RD

29

DampPosMin_SC

percent (98)

x

x

x

x

x

x

RD

30

DampPosMax_TS

percent (98)

x

x

x

x

x

x

RD

31

DampPosMin_TS

percent (98)

x

x

x

x

x

x

RD

32

VolflowSet_R

l/s (87)







WR, RD

33

PressSet

pascal (57)







WR, RD

34

Volt_AI2

volt (5)

x

x

x

x

x

x

RD

35

Volt_AI3

volt (5)

x

x

x

x

x

x

RD

36

Volt_AO2

volt (5)

x

x

x

x

x

x

WR, RD

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Binary Value Objects

Instance Designation Unit Access
Instance Designation TCU3 TAM Access
Instance Designation Available with equipment function Access
Instance Designation FH RR RR RMF EC, SC TAM TAM RMF Access

1

LocalAlarm (COVU)

x

x

x

x

x

x

RD

2

SummaryAlarm (COVU)



x



x

RD

3

PressAlarm (COVU)



x



x

RD

4

ManOP_Disable

x1


x



x

WR, RD

5

PressSetSel



x



x

WR, RD

6

DI1

x

x

x

x

x

x

RD

7

DI2

x

x

x

x

x

x

RD

8

DI3

x

x

x

x

x

x

RD

9

DI4

x

x

x

x

x

x

RD

10

DI5

x

x

x

x

x

x

RD

11

DI6

x

x

x

x

x

x

RD

12

DO1

x

x

x

x

x

x

RD

13

DO2

x

x

x

x

x

x

RD

14

DO3

x

x

x

x

x

x

RD

15

DO4

x

x

x

x

x

x

RD

16

DO5

x

x

x

x

x

x

RD

17

DO6

x

x

x

x

x

x

RD

18

SC_Alarm







RD

19

DO1_Set

x

x

x

x

x

x

WR, RD

20

DO2_Set

x

x

x

x

x

x

WR, RD

21

DO3_Set

x

x

x

x

x

x

WR, RD

22

DO4_Set

x

x

x

x

x

x

WR, RD

23

DO5_Set

x

x

x

x

x

x

WR, RD

24

DO6_Set

x

x

x

x

x

x

WR, RD

25

DO1_SetByLocal

x

x

x

x

x

x

RD

26

DO2_SetByLocal

x

x

x

x

x

x

RD

27

DO3_SetByLocal

x

x

x

x

x

x

RD

28

DO4_SetByLocal

x

x

x

x

x

x

RD

29

DO5_SetByLocal

x

x

x

x

x

x

RD

30

DO6_SetByLocal

x

x

x

x

x

x

RD

1 only for individually selected operating mode (stand-alone operation)

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Modbus interface

Application

The expansion module EM-BAC-MOD supports the following interface functions on an EASYLAB controller TCU3 or an adapter module TAM if the Modbus protocol has been selected:

  • Modbus is an open serial master-slave communication protocol which has become a de facto standard for the industry
  • The master (e.g. central BMS) can address a number of slaves (EASYLAB volume flow controllers) and use Modbus functions to request information from individual data points
  • Data access is based on numbered data registers which the master has to define in order to request data using Modbus functions
  • The slave responds by either returning the requested information or an exception code (error)
  • Example: The Read Holding Registers function (register no. 3) returns the volume flow rate actual value of the addressed controller
  • General information for a Modbus device can be read out using the Read Device Identification function

Modbus functions

Function no. Designation Meaning

1 (0x01)

Read Coils

Read states of 1 to 8 bits according to bit list

3 (0x03)

Read Holding Registers

Read several consecutive registers

4 (0x04)

Read Input Registers

Read several consecutive registers

5 (0x05)

Write Single Coil

Write state of a single bit

6 (0x06)

Write Single Register

Write single register

8 (0x08)

Diagnostics

Check Modbus communication

16 (0x10)

Write Multiple Registers

Write several consecutive registers

43 (0x2B)

Read Device Identification

Read identification data for the device

14 (0x0E)

Read Device Identification

Read identification data for the device


Exception codes

Codes Designation Meaning

1

Illegal Function Code

Unknown function or subfunction code

2

Illegal Data Address

Invalid register address

3

Illegal Data Value

Inconsistent coding for number of registers/bytes, data value

Exception codes (error codes) are returned in case of invalid function or register access.


Bit list for ReadCoil/WriteSingleCoil functions

Bit Unit Access
Bit TCU3 TAM Access
Bit Available with equipment function Access
No. Designation FH RR RR-RMF EC, SC TAM TAM-RMF Access

0

ManOP_Disable

x1


x



x

WR

1

PressSetSel



x



x

WR

2

Local Alarm

x

x

x

x

x

x

RD

3

SummaryAlarm



x



x

RD

4

PressAlarm



x



x

RD

5

SC_SetlockHighPrio







WR

6

SC_GetLockHighPrio







RD

7

SC_Alarm







RD

1 only for individually selected operating mode (stand-alone operation)

Bits are read with function 1 (RD) or written with function 5 (WR).

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Register list for Read***Registers and Write***Registers functions

Register Unit Access
Register TCU3 TAM Access
Register Available with equipment function Access
No. Designation FH RR RR-RMF EC, SC TAM TAM-RMF Access

0

Mode

x1

 

x



x

WR

1

ManOP_Disable

x1

 

x



x

WR

2

ModeAct

x

x

x

x



RD

3

VolflowAct

x

x

x

x



RD

4

VolflowSet

x

x

x

x



RD

5

VelocityAct

x

 





RD

6

VelocitySet

x

 





RD

7

VolTotalExh

x

x

x

x

x

x

RD

8

VolTotalSup

x

x

x

x

x

x

RD

9

VolOffset_T

 

 

x



x

WR

10

VolOffset_P

 

 

x



x

WR

11

PressAct

 

 

x



x

RD

12

PressSet

 

 

x



x

RD

13

PressSetSel

 

 

x



x

WR

14

DampPos

x

x

x

x



RD

15

DampPosMax_FH - Value

x

x

x

x

x

x

RD

16

DampPosMax_FH - Status

x

x

x

x

x

x

RD

17

DampPosMin_FH - Value

x

x

x

x

x

x

RD

18

DampPosMin_FH - Status

x

x

x

x

x

x

RD

19

DampPosMax_RE - Value

x

x

x

x

x

x

RD

20

DampPosMax_RE - Status

x

x

x

x

x

x

RD

21

DampPosMin_RE - Value

x

x

x

x

x

x

RD

22

DampPosMin_RE - Status

x

x

x

x

x

x

RD

23

DampPosMax_TE - Value

x

x

x

x

x

x

RD

24

DampPosMax_TE - Status

x

x

x

x

x

x

RD

25

DampPosMin_TE - Value

x

x

x

x

x

x

RD

26

DampPosMin_TE - Status

x

x

x

x

x

x

RD

27

DampPosMax_RS - Value

x

x

x

x

x

x

RD

28

DampPosMax_RS - Status

x

x

x

x

x

x

RD

29

DampPosMin_RS - Value

x

x

x

x

x

x

RD

30

DampPosMin_RS - Status

x

x

x

x

x

x

RD

31

LocalAlarm

x

x

x

x

x

x

RD

32

SummaryAlarm

 

 

x



x

RD

33

PressAlarm

 

 

x



x

RD

34

WireSensorPos

x

 





RD

35

SwitchPos

x

 





RD

36

RoomModeAct

 

 

x



x

RD

37

SystemDevices

x

x

x

x

x

x

RD

38

SunBlind

 

 

x



x

WR

39

StateDI

x

x

x

x

x

x

RD

40

StateDO

x

x

x

x

x

x

RD

41

VolflowExh

x

x

x


x

x

WR

42

VolflowSup

x

x

x


x

x

WR

43

SC_SetLockHighPrio







WR

44

SC_GetLockHighPrio







RD

45

SC_SetPos - Value







WR

46

SC_SetPos - Status







WR

47

SC_GetPos







RD

48

SC_Alarm







RD

49

DampPosMax_EC - Value

x

x

x

x

x

x

RD

50

DampPosMax_EC - Status

x

x

x

x

x

x

RD

51

DampPosMin_EC - Value

x

x

x

x

x

x

RD

52

DampPosMin_EC - Status

x

x

x

x

x

x

RD

53

DampPosMax_SC - Value

x

x

x

x

x

x

RD

54

DampPosMax_SC - Status

x

x

x

x

x

x

RD

55

DampPosMin_SC - Value

x

x

x

x

x

x

RD

56

DampPosMin_SC - Status

x

x

x

x

x

x

RD

57

DampPosMax_TS - Value

x

x

x

x

x

x

RD

58

DampPosMax_TS - Status

x

x

x

x

x

x

RD

59

DampPosMin_TS - Value

x

x

x

x

x

x

RD

60

DampPosMin_TS - Status

x

x

x

x

x

x

RD

61

DO_Set

x

x

x

x

x

x

WR

62

DO_SetByLocal

x

x

x

x

x

x

RD

63

VolflowSet_R







WR, RD

64

PressSet







WR, RD

65

Volt_AI2

x

x

x

x

x

x

RD

66

Volt_AI3

x

x

x

x

x

x

RD

67

Volt_AO2

x

x

x

x

x

x

WR, RD

1 only for individually selected operating mode (stand-alone operation)

FH: Fume cupboard controller

RR: Room controller for supply air or extract air (RS, RE, PC)

RR RMF: Room controller with active room management function

EC, SC: Single controller for supply air or extract air (EC, SC)

TAM: Adapter module

TAM RMF: Adapter module with active room management function


Data points – detailed description

The following is a detailed description of the information that each data point provides; input variables and output variables are described separately:

  • Name of data point
  • Access as viewed from the central BMS
  • WR – Defaults for the volume flow controller or room, from the central BMS
  • RD – Data provided by the volume flow controller or room
  • List of volume flow controller equipment functions for which the variable is available
  • Unit of measure (applies only to BACnet objects of type Analogue Value Object)
  • Function and special functional values with their meaning
  • Access to the data point using a BACnet object or Modbus register

Installation details

  • Installation details

Installation and commissioning

Installation

  • As attachment for the EASYLAB base component: factory mounted
  • For retrofitting: Mount the expansion module into the base casing
  • Make connection to the BACnet/Modbus EIA-485 network


Commissioning

  • The EASYLAB controller identifies the expansion module automatically
  • Select BACnet or Modbus protocol using slide switch
  • Set network address and communication parameters using the coding switches
  • If necessary, activate terminal resistor of the network segment
  • Integrate data interface with the central BMS (system integration)

Téléchargements

Information produit

Certificats

Manuels d'utilisation

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Partager la page

Recommander cette page

Vous avez la possibilité de recommander cette page en partageant le lien.

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Votre recommandation a été envoyée et sera bientôt reçue par le destinataire.

Contact

Nous sommes à votre disposition

Veuillez spécifier le sujet de votre requête et vos coordonnées.
Tel.: +33 1 56 70 54 54

Pièce jointe (max. 10MB)

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été reçu par le Centre de Service et est en cours de traitement.
Notre département des demandes de service vous contactera sous peu.
Si vous avez des questions d'ordre général sur nos produits et services, vous pouvez également nous contacter à l'adresse suivante:
Tél .: +49 (0) 2845 2020 | Fax: +49 (0) 2845 202265

Contact

Nous sommes à votre disposition

Veuillez spécifier le sujet de votre requête et vos coordonnées.
Tel.: +33 1 56 70 54 54

Pièce jointe (max. 10MB)

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été reçu par le Centre de Service et est en cours de traitement.
Notre département des demandes de service vous contactera sous peu.
Si vous avez des questions d'ordre général sur nos produits et services, vous pouvez également nous contacter à l'adresse suivante:
Tél .: +49 (0) 2845 2020 | Fax: +49 (0) 2845 202265