Duct pressure control - static transducer
Application
Control strategy
Operating modes
Variable operation (V)
Constant value mode (F)
Interface
Analogue interface with adjustable signal voltage range
Signal voltage ranges
Operating parameters
Parts and characteristics
Note:
Differential pressure connections on the outside of the control unit are not accessible with this attachment depending on the variant, e.g. acoustic cladding.
Construction
GUAC-PM6 with spring return actuator 341C-024-05-V/ST06 for:
▪ TVR, TZ-Silenzio, TA-Silenzio, TVZ, TVA,
▪ TVRK up to NW 250
GUAC-PM6 with spring return actuator 361C-024-20-V/ST06 for:
▪ TVJ
▪ TVT up to dimensions of 1000 x 600
▪ TVRK from NW 315
Commissioning
Useful additions
A static differential pressure transducer converts the duct pressure into a voltage signal. The differential pressure actual value is available as a voltage signal. The factory setting is such that 10 V DC always corresponds to the nominal differential pressure (Δp nom). The differential pressure setpoint value is either a constant value or it comes from a setpoint adjuster or from switch contacts. The controller compares the differential pressure setpoint value to the actual value and controls the actuator accordingly if there is a difference. Differential pressure parameters and signal voltage range are stored in the control component. Customers can easily make changes using an adjustment device or a notebook with service tool. If the supply voltage is interrupted or a wire breaks, the spring return actuator moves to the safe position OPEN (NO) or CLOSED (NC) as specified in the order code.
Category
Application
Area of application
Actuator
Installation orientation
Connection
Supply voltage
Interface/signalling
Interface information
Special functions
Parameter setting
TVR | – | D | / | 200 | / | D2 | / | XF4 | / | PDS | / | V | 0 | / | Pmin | – | Pmax | Pa | / | NC |
| | | | | | | | | | | | | | | | | | | | |||||||||||
1 | 2 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | |||||||||||
Acoustic cladding | Without |
Material | Galvanised sheet steel |
Nominal size | 100 mm |
Accessories | Double lip seal both sides |
Attachment | Universal controller for duct pressure, spring return actuator |
Equipment function/installation location | Duct pressure control, supply air |
Operating mode | Variable operation – signal voltage range 0 –10 V DC |
Operating value | 300 – 500 Pa |
Damper blade position | NO, Power off to OPEN |
Compact controllers for VAV terminal units
– | Controller | Spring return actuator | – | ||
Order code detail | Part number | Type | Part number | Type | VAV terminal units |
XF4 | A00000038354 | GUAC-PM6 | A00000038357 | 341C-024-05-V/ST06 | ① |
XF4 | A00000038354 | GUAC-PM6 | A00000038355 | 361C-024-20-V/ST06 | ② |
① TVR, TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVRK up to NW 250
② TVJ, TVT up to dimensions 1000 x 500, TVRK from NW 315
Differential pressure controller GUAC-PM6
Supply voltage (AC) | 24 V AC ± 20%, 50/60 Hz |
Supply voltage (DC) | 24 V DC ± 20 % |
Power rating (AC) | 5 VA max. |
Power rating (DC) | Max. 2.5 W plus actuator used * |
Nominal pressure range | 0 – 600 Pa plus actuator used * |
Pressure control range | 25 – 550 Pa |
Torque | 15 Nm |
Input for setpoint value signal or override control | 0 – 10 V DC, Ra > 100 kΩ or 2 – 10 V DC, |
Actual value signal output | 0 – 10 V DC or 2 – 10 V DC, |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 42 |
EC conformity | EMC to 2014/30/EU |
Weight | 0.570 kg |
* When dimensioning the transformers and the supply cable for the universal controller, the power consumption of the associated actuator must be taken into account.
** Input can be connected to supply voltage as part of override control.
Actuator with spring return 341C-024-05-V/ST06
Supply voltage | From the controller |
Power consumption for motor (movement) | 5.0 W |
Standby power consumption (end position) | 2.0 W |
Rating | 7.5 VA |
Torque | 5 Nm |
Run time for 90° | 100 s |
Spring return time | < 20 s |
Setpoint value signal input | From the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 (cable entry at the bottom) |
EC conformity | EMC to 2014/30/EU |
Weight | 1.3 kg |
Actuator with spring return 361C-024-20V/ST06
Supply voltage | From the controller |
Power consumption for motor (movement) | 8.0 W |
Standby power consumption (end position) | 2.0 W |
Rating | 11.5 VA |
Torque | 20 Nm |
Run time for 90° | 150 s |
Spring return time | < 20 s |
Setpoint value signal input | From the controller |
IEC protection class | III (protective extra-low voltage) |
Protection level | IP 54 |
EC conformity | EMC to 2014/30/EU |
Weight | 1.6 kg |
Range of display functions
Display functions
Setting options
Diagnostic function
Commissioning
Analogue interface 0 – 10 V or 2 – 10 V DC (operating mode V, F)
The analogue interface can be adjusted for the signal voltage range 0 – 10 V DC or 2 – 10 V DC. The assignment of the duct pressure setpoint value or actual value for voltage signals is shown in the characteristic curves.
Setpoint value setting
Variable operation
Constant value mode
Actual value as feedback for monitoring or tracking control
Override control
For special operating situations, the duct pressure controller can be put in a special operating mode (override control). The following modes are possible: control Pmin, control Pmax, damper blade in the OPEN position, damper blade CLOSED.
Under certain conditions the control can also be suspended (control stop).
Override control via signal input Y
Override control CLOSED via control signal Y
Override controls for diagnostic purposes
Prioritisation of various setting options
Spring return actuator
Partager la page
Recommander cette page
Vous avez la possibilité de recommander cette page en partageant le lien.
Contact
Merci pour votre message !
Votre recommandation a été envoyée et sera bientôt reçue par le destinataire.
Contact
Nous sommes à votre disposition
Veuillez spécifier le sujet de votre requête et vos coordonnées.
Tel.: +33 1 56 70 54 54
Contact
Merci pour votre message !
Votre message a été reçu par le Centre de Service et est en cours de traitement.
Notre département des demandes de service vous contactera sous peu.
Si vous avez des questions d'ordre général sur nos produits et services, vous pouvez également nous contacter à l'adresse suivante:
Tél .: +49 (0) 2845 2020 | Fax: +49 (0) 2845 202265
Contact
Nous sommes à votre disposition
Veuillez spécifier le sujet de votre requête et vos coordonnées.
Tel.: +33 1 56 70 54 54
Contact
Merci pour votre message !
Votre message a été reçu par le Centre de Service et est en cours de traitement.
Notre département des demandes de service vous contactera sous peu.
Si vous avez des questions d'ordre général sur nos produits et services, vous pouvez également nous contacter à l'adresse suivante:
Tél .: +49 (0) 2845 2020 | Fax: +49 (0) 2845 202265