XM0_mit_Kappe_querpsd.png
Compact controller XM0 for TVE and TVE-Q
Modbus_XM0png.png

Bus interface Modbus RTU

BM0-J6_img_05psd.png
X-AIR-ZMAS

X-AIRCONTROL Modbus zone module

XM0_RJ12_Steckerjpg.jpg
Room control

RJ12 socket

XS0_img_01png.png

Control component for type TVE

TVE-Q_-P1_img_02psd.png
VAV control unit variant TVE-Q-P1 (powder-coated)

Control component for type TVE

XM0_mit_Kappe_querpsd.png
Modbus_XM0png.png
BM0-J6_img_05psd.png
XM0_RJ12_Steckerjpg.jpg
XS0_img_01png.png
TVE-Q_-P1_img_02psd.png

XM0-J6 

CONTROL COMPONENT WITH DYNAMIC TRANSDUCER AND MODBUS RTU INTERFACE FOR X-AIRCONTROL

Compact device for VAV terminal unit TVE and TVE-Q

  • Controller, dynamic differential pressure transducer and actuator in one casing
  • Use in ventilation and air conditioning systems, only with clean air
  • Simple RJ12 connection socket for supply voltage and network
  • Compatible with the X-AIRCONTROL zone module Modbus
  • Volume flow rates qvmin and qvmax are pre-set in the factory and saved in the controller as variable parameters
  • High data transparency via standardised bus communication Modbus RTU, RS485
  • Setpoint value settings, override controls, parameter adjustment via Modbus register
  • Integrated display for volume flow rate display, operating status display and setting of operating parameters
  • Service access for manual adjustment devices and PC configuration software

General information

Application

  • All-in-one control devices for VAV terminal units types TVE and TVE-Q
  • Dynamic differential pressure transducer, electronic controller and actuator are combined in one casing
  • For clean air in ventilation and air conditioning systems
  • The standard filtration enables use in the supply air without additional dust protection measures
  • Application examples: Offices and classrooms
  • In the event of a strong occurrence of dust, install appropriate extract air filters upstream, as a partial volume flow is routed through the transducer for volume flow rate measurement.
  • If the air is heavily contaminated with dust, fluff, or sticky and moist components, an attachment with a static differential pressure transducer must be used, e.g. XS0-J6
  • Application examples: Extract air from changing areas and showers, hospital bedrooms
  • Various control options based on setpoint value default setting
  • Suitable for X-AIRCONTROL room control, Modbus zone module
  • Control circuits for e.g. temperature, humidity, and air quality control the variable volume flow by specifying setpoint values via the communication interface
  • Simple connection for supply voltage and network with one shared RJ12 terminal socket
  • Override control for activating qvmin, qvmax, shut-off, OPEN position, possible via the Modbus register
  • The actual volume flow rate value is available as a network data point
  • The damper blade position is available as a network data point


Control strategy

  • The volume flow controller works independently of the duct pressure
  • Differential pressure fluctuations do not result in permanent volume flow rate changes
  • To prevent the control from becoming unstable, a dead zone (hysteresis) is maintained, in which the damper blade is not moved
  • The flow rate range for the controller is set in the factory (qvmin: minimum volume flow rate, qvmax: maximum volume flow rate)
  • Operating parameters are defined by the order code and parameterised at the factory


Operating modes

  • Modbus (M): setpoint value specification via X-AIRCONTROL


Communication interface

  • Modbus RTU, RS 485
  • Data point list see Modbus register list


Parts and characteristics

  • Transducer based on dynamic measuring principle. It can only be used with clean air, as a partial volume flow is passed through the transducer
  • Overload-proof actuator
  • RJ12 connection socket with cover
  • Display and control elements for easy menu navigation
  • Menu navigation allows for adjusting operating parameters and communication interface
  • Service interface


Construction

  • TR0VM-024T-05I-DD15-MB with RJ12 connection socket
  • Can only be used for type TVE and TVE-Q


Commissioning

  • As the volume flow rates are factory-set, the control units have to be installed at the specified locations only
  • Network integration requires commissioning steps
  • Operating parameters can be adjusted on site (using the display, an adjustment device, or the Modbus register)


Useful additions

  • Adjustment device type GUIV3-M (order code AT-VAV-G3)
  • Room control X-AIRCONTROL with zone module Modbus type X-AIR-ZMO-MOD

Information technique

Function, Specification text, Order code

  • FUNCTION
  • SPECIFICATION TEXT
  • ORDER CODE
XS0_dia_01ai.png

1 Differential pressure transducer
2 Actuator
3 Volume flow controller
4 Setpoint value via BACnet, Modbus or analogue signal
5 Shaft with effective pressure channel

Air terminal units control the volume flow in a closed loop, which means: measurement – comparison – adjustment.
The volume flow rate is obtained by measuring a differential pressure. This is effected via a differential pressure sensor. The integrated differential pressure transducer converts the differential pressure into a voltage signal. The actual volume flow value is available as a data point. Du to the factory adjustment, 100% always equals the nominal volume flow rate (qvNom).
The volume flow setpoint value is specified by a higher-level controller (e.g. room temperature controller, air quality controller, central BMS). Variable volume flow control can be set betweenvmin and qvmax. It is possible to override the room temperature control by forced switching, e.g. for a shut-off
The controller compares the volume flow setpoint with the current actual value and adjusts the internal actuator according to the control deviation.

Category

  • Compact controller for volume flow rate
  • Control of a constant or variable volume flow rate setpoint
  • Electronic controller for connecting a reference variable and recording an actual value for integration into X-AIRCONTROL
  • The actual value relates to the nominal volume flow rate so that commissioning and subsequent adjustment are simplified


Application

  • Dynamic transmitter for clean air in ventilation and air conditioning systems



Supply voltage



  • 24 V AC/DC



Actuator

  • Integral; slow-running (running time 100 s for 90°)


Installation orientation

  • Not critical


Interface/signalling

  • Modbus RTU (RS-485)



Connection

  • RJ12 connection socket for easy connection to X-AIRCONTROL, with rubber cap cover
  • Suitable for X-AIRCONTROL zone module X-AIR-ZMO-MOD


Interface information

  • Modbus: includes writing and reading of volumetric flow setpoint and actual value signal, damper position, override control


Special functions

  • Clearly visible external indicator light for indicating the functions: Set, not set, and power failure
  • Display for actual values, parameter setting and for test functions
  • Activation qvmin, qvmax, closed, open by X-AIRCONTROL


Parameter setting

  • Specific parameters for VAV terminal unit are factory-set
  • Operating values: qvmin, qvmax are factory-set
  • Subsequent adjustment via display and operating element directly on the unit or with optional tools: Setting device, PC software (each wired), in Modbus mode also via Modbus register access


Factory condition

  • Electronic controller factory-mounted on the terminal unit
  • Factory set parameters
  • Functional test under air; certified with sticker


TVED – P1FL / 100 / G2 / XM0-J6 / M/20 – 350 [m³/h]
||   ||||||
|
12  3 45678
10

1 Type
TVE VAV terminal unit

2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding

3 Material
No entry: Galvanised sheet steel
P1 Surface powder-coated, RAL 7001 (silver grey)
A2 Stainless steel construction

4 Air duct connection
No entry: Push-fit end, suitable for air ducts according to EN
1506; with groove for optional seal
FL Flanges on both ends

5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400

6 Accessories

No entry: without accessories
D2 Double lip seal both ends (only for push-fit end with groove)
G2 Matching flange for every flange (only with FL)

7 Attachment (control component)
XM0-J6 Volume flow controller with dynamic transducer, display,
Modbus RTU interface, RJ12 socket (for X-AIRCONTROL)

8 Operating mode
M Modbus RTU interface, variable operation (default setpoint value via Modbus register)

10 Operating values for factory setting
Volume flow rate [m³/h or l/s]
qᵥmin – qᵥmax

Order example: TVE/100/D2/XM0-J6/M/20-350 m³/h
Acoustic claddingwithout
Materialgalvanised sheet steel
Nominal size100 mm
AccessoriesDouble lip seal both ends
Attachment (control components)Compact controller volume flow, dynamic transmitter,
Interface Modbus RTU, display, RJ12 connection socket (for X-AIRCONTROL)
Operating modeModbus RTU
Volume flow rate20 – 350 m³/h

Variants

  • Variants

  • TVE

Technical data

  • Technical data


Compact controllers for VAV terminal units

Part number

Type of installation component

VAV terminal units

A00000069230TR0VM-024T-05I-DD15-MBTVE, TVE-Q


Compact controller TR0VM-024T-05I-DD15-MB with RJ12 connection socket

Type of measurement/installation orientationDynamic measurements, any installation orientation
Supply voltage (AC)24 V AC, ± 20 %, 50/60 Hz
Supply voltage (DC)24 V DC ± 20 %
Power rating (AC)NW 100 – 160: maximum 4 VA
NW 200 – 400: maximum 7 VA
TVE-Q up to height 200: maximum 4 VA
TVE-Q from height 300: maximum 7 VA
Power rating (DC)NW 100 – 160: maximum 2.5 W
NW 200 – 400: maximum 4 W
TVE-Q up to height 200: maximum 2.5 W
TVE-Q from height 300: maximum 4 W
Power consumption (when running/when idle)

1 W

Run time for 90°100 s
IEC protection classIII (Protective extra-low voltage)
Protection levelIP 42 (with attached terminal cover)
EC conformityEMC to 2014/30/EU
Bus connectionModbus RTU, RS485
Number of nodes128
Adjustable communication parameters1200 – 115,200 Bd
Start bit: 1
Data bits: 8
Stop bits: 1 or 2
Parity: None, Even, Odd
Setpoint / actual value interface (Modbus)

Via X-AIRCONTROL/Modus register list

Cable terminationexternally required

 

Interface configuration of the control component


The communication interface for the control component is pre-set to Modbus at the factory for use with the X-AIRCONTROL zone module. Only the Modbus address must be set by the customer, depending on the use in the supply air and extract air. For other applications, data transmission speed and format must be adapted on site according to the network environment.


 

XM0–J6

Setpoint value default setting via:Actual values via:corresponds to order key optionMenu configuration (Mode)
Analogue operation *analogue 0 - 10 Vanalogue 0 - 10 VV or FCA0
Analogue operation *analogue 2 - 10 Vanalogue 2 - 10 VV or FCA2
Modbus operationModbus register setpointModbus register actual value or analogue 2 - 10 VMCB


* It is not possible to use the analogue interface in combination with the RJ12 connection socket provided with the XM0-J6 variant. Therefore, the configuration register 122 (interface mode) must not be changed on site. To use an analogue interface, type XM0 must be installed.


Téléchargements

Information produit

Certificats

production {"X-Frame-Options"=>"SAMEORIGIN", "X-XSS-Protection"=>"1; mode=block", "X-Content-Type-Options"=>"nosniff", "X-Download-Options"=>"noopen", "X-Permitted-Cross-Domain-Policies"=>"none", "Referrer-Policy"=>"strict-origin-when-cross-origin", "Strict-Transport-Security"=>"max-age=31536000; includeSubDomains", "Content-Type"=>"text/html; charset=utf-8"}

Partager la page

Recommander cette page

Vous avez la possibilité de recommander cette page en partageant le lien.

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Votre recommandation a été envoyée et sera bientôt reçue par le destinataire.

Contact

Nous sommes à votre disposition

Veuillez spécifier le sujet de votre requête et vos coordonnées.
Tel.: +33 1 56 70 54 54

Pièce jointe (max. 10MB)

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été reçu par le Centre de Service et est en cours de traitement.
Notre département des demandes de service vous contactera sous peu.
Si vous avez des questions d'ordre général sur nos produits et services, vous pouvez également nous contacter à l'adresse suivante:
Tél .: +49 (0) 2845 2020 | Fax: +49 (0) 2845 202265

Contact

Nous sommes à votre disposition

Veuillez spécifier le sujet de votre requête et vos coordonnées.
Tel.: +33 1 56 70 54 54

Pièce jointe (max. 10MB)

Les champs marqués d'une étoile (*) sont obligatoires.

Contact

Merci pour votre message !

Votre message a été reçu par le Centre de Service et est en cours de traitement.
Notre département des demandes de service vous contactera sous peu.
Si vous avez des questions d'ordre général sur nos produits et services, vous pouvez également nous contacter à l'adresse suivante:
Tél .: +49 (0) 2845 2020 | Fax: +49 (0) 2845 202265